Automatic Well Testing

Problems

  • Previous integrator abandoned project before it was 100% complete.
  • Reported values for water, gas, and oil volumes were incorrect.
  • HMI was largely unreadable due to poor color choices and font sizes.
  • Field devices were not installed according to the National Electric Code.
  • Field devices were not calibrated correctly.
  • Flow rate for the Phase Dynamics water cut monitor was not within specs, which yielded an incorrect water cut.

Solutions

  • Modified calculations in PLC program to yield correct results.
  • Modified HMI to use high-contrast colors and larger font sizes.
  • Reinstalled field devices to comply with local and Federal codes.
  • Tested and calibrated all field devices.
  • Coordinated with Phase Dynamics to modify update interval from 5 seconds to 2 seconds.
  • Modified flow control parameters to bring flow rate within Phase Dynamics specs.

Results

  • Increased product quality.
  • More productive employees.
  • More reliable equipment.
  • Better able to document environmental compliance.

Details

Client: BreitBurn Energy
Location: Orcutt, CA

PLCs:
  • (2) Automation Direct - Productivity 3000
  • 38 discrete, 16 analog
HMIs:
  • (2) Maple Systems - 4.3" color touchscreen - 5043T
  • 65 tagnames
Remote Alarming:
  • none
Data Historian:
  • none
Other Components Integrated through SCADA:
  • Phase Dynamics - water cut monitor
Networking, Protocols, and Drivers:
  • Modbus RTU
  • TCP/IP
  • EIA-568A
  • RS-485